Prof.Dr.H.Ziegler CEN/TC176-WG4-N107 Rev.4

Proposal for future M-Bus Application Layer

1. Introduction

The M-Bus application layer describes a standard especially for meter readout. It can be used with various physical layers and with link layers and network layers which support the transmission of variable length binary transparent telegrams. The first byte of an application layer telegram is the CI-field which distinguishes between various telegram types and application functions. It is also used to distinguish between true application layer communication and management commands for lower layers. The meaning of the remaining bytes of the telegram depends also on the value of the CI-field. This second revision is a compatible enhancement of the sections 6.4 to 6.6 of the original standard EN1434-part 3 (1997). Besides some clarifications and implementation hints it contains optional enhancements especially for complex meters. Due to technical progress some variants (Fixed format and mode 2=high byte first) are no longer recommended for new developments but are still included as a reference.

Note that this standard contains only directions how data should be coded. It is beyond the task of an application layer standard to define which data must be transmitted under what conditions by which types of slaves or which data transmitted to a slave must have which reactions. Therefore adherence to this standard guarantees the coexistance and common communication and readout capability of slaves via a universal master software (covering all optional features), but not yet functional or communication interchangeabilty of meters following this standard. For several meter types and meter classes the company "Fernwärme Wien" and the "AGFW"-group of remote heating users have provided such application descriptions required for full interchangeability. They are accessible via the www-server of the m-bus users group (http://www.m-bus.com).

2. CI-Field

2.1 OverviewMaster to slave

The original EN1434-3 defined two possible data sequences in multibyte records. The bit two (value 4), which is called M bit or Mode bit, in the CI field gives an information about the used byte sequence in multibyte data structures. If the Mode bit is not set (Mode 1), the least significant byte of a multibyte record is transmitted first, otherwise (Mode 2) the most significant byte. The Mode 2 (M=1) is obsolete and should not be used. It is documented here only as a reference for universal master software with support of old meters.

 

 

Mode 1

(Mode 2)

Application

00h-4Fh

 

reserved for DLMS

50h

 

application reset

51h

(55h)

data send (master to slave)

52h

(56h)

selection of slaves

53h

 

reserved

54h-58h

 

reserved for DLMS

59h-5Bh

 

reserved

5Ch

 

synchronize action

60h-6Fh

 

reserved

70h-7Fh

(74h)

reserved for answer directionslave to master: report of application errors

71h

 

slave to master: report of alarms

72h

(76h)

slave to master: Variable format data respond

73h

(77h)

slave to master: Fixed format data respond

7880h-8Fh

 

reserved

90h-97h

 

manufacturer specific (obsolete)

A0h-AFh

 

manufacturer specific

B0-B7h

 

manufacturer specific (obsolete)

B8h

 

set baudrate to 300 baud

B9h

 

set baudrate to 600 baud

BAh

 

set baudrate to 1200 baud

BBh

 

set baudrate to 2400 baud

BCh

 

set baudrate to 4800 baud

BDh

 

set baudrate to 9600 baud

BEh

 

set baudrate to 19200 baud

BFh

 

set baudrate to 38400 baud

C0h-FFh

 

reserved

Table 1 CI-Field codes used by the master

"Reserved for DLMS" refers to the DLMS PDUīs in A-XDR encoding of the FDIS version of the IEC-DLMS standard. Choosing CI-fields different from these code simplifies the construction of slaves which can have dual application layers for both standards and which then can automatically distinguish between communication according to both standards.

Note that the CI-codes $50, $52/$56, $5C, $70/$74, $71, $A0-$AF and $B8-$BF are optional compatible enhancements of the original standard. Note also that even if the functions of these optional CI-codes are not implemented in a slave the link layer protocol requires a proper link layer acknowledge of SND_UD telegrams containing any of these CI-codes.

2.1.2 Application reset (CI = $50), (optional)

With the CI-Code $50 the master can release a reset of the application layer in the slaves. Each slave himself decides which parameters to change - e.g. which data output is default - after it has received such an application reset. This application reset by a SND_UD with CI=$50 is the counterpart to the reset of the data link layer by a SND_NKE.

2.2.1.3 Application reset subcode (optional)

It is allowed to use optional parameters after CI = $50. If more bytes follow, the first byte is the application reset subcode. Further bytes are ignored. The application reset subcode defines which telegram function and which subtelegram is requested by the master. The datatype of this parameter is 8 bit binary. The upper 4 bits define the telegram type or telegram application and the lower 4 bits define the number of the subtelegram. The lower four bits may me ignored for slaves which provide only a single telegram for each application. The use of the value zero for the number of the subtelegram means that all telegrams are requested.

Slaves with only one type of telegram may ignore application reset and the added parameters but have to confirm it ($E5).

The following codes can be used for the upper 4 bits of the first parameter:

Coding

Description

Examples

0000b

All

 

0001b

User data

consumption

0010b

Simple billing

actual and fixed date values+dates

0011b

Enhanced billing

historic values

0100b

Multi tariff billing

 

0101b

Instaneous values

for regulation

0110b

Load management values for management

 

0111b

Reserved

 

1000b

Installation and startup

bus adress, fixed dates

1001b

Testing

high resolution values

1010b

Calibration

 

1011b

Manufacturing

 

1100b

Development

 

1101b

Selftest

 

1110b

Reserved

 

1111b

Reserved

 

Table 2 Coding of the upper four bits of the first parameter after CI = $50

Note that this table has been expanded with optional elements from the original standard.

 

2.3 Master to slave data send (51h/55h) (optional)

The CI-Field codes 51h(55h) are used to indicate the data send from master to slave:

Variable Data Blocks (Records)

MDH(opt)O

Opt.Mfg.specific data Opt)

variable number

1 Byte

variable number

Fig. 1 Variable Data Structure master to slave

Note that this structure is identical to the slave to master direction (see chapter 4) with the exception of the fixed header which is omitted in this direction.

2.4 Slave select (52h/56h) (optional)

The CI-Field codes 52h(56h) are used for the management of an optional netwerk layer using secondary adressing (See chapter 9).

2.51.4 Synchronize action (CI = $5C) (optional)

This CI-code can be used for synchronizing functions in slaves and masters (e.g. clock synchronization). Special actions or parameter loads may be prepared but their final execution is delayed until the reception of such a special CI-field command.

2.2 Slave to master (answer) codes

The following codes can be used for the direction slave to master:

CI M=0

CI M=1

Application

70h

(74h)

report of general application errors

71h

 

report of alarm status (See Appendix)

72h

(76h)

variable data respond

73h

(77h)

fixed data respond

Table 3 CI-Field codes used by the slave

The use of these control information codes is described in the chapters 3 (fixed data respond), 4 (variable data respond), 6.6 (report of general application errors) and 8.1 (report of alarm status).

2.6 Report of application errors (slave to master) (CI = $70/74) (optional)

3 Fixed Data Structure

For details of the report of application errors see chapter 6.

2.7 Report of alarm status (slave to master) (CI = $71) (optional)

For details of the report of alarm status errors see appendix C.

2.8 Fixed and variable data respond (slave to master) (CI = $72/$76 and $73/$77)

In the reply direction (slave to master) with a long frame originally two different data structures were used. The fixed data structure, besides a fixed length, is limited to the transmission of only two counter states of a predetermined length, which have binary or BCD coding. In contrast the variable data structure allows the transmission of more counter states in various codes and further useful information about the data. The number of bytes of the transmitted counter states is also variable with this data structure. Contrary to the fixed structure, the variable structure can also be used in calling direction. For theseis reasons the fixed data structure is not recommended for future developments. For information on this obsolete fixed data structure see appendix D. For new development therefore only the CI-field $72 shall be used. This is a restriction from the original standard.

To identify the fixed data structure, the numbers 73h/77h for the control information field are used. In this way a universal master software can see how it must interpret the data. For further details on the structure of telegrams starting with CI-values of $72/($76) see chapter 3.

2.9 Baudrate switch commands $B8-$BF (optional)

These optional commands can be used by a master to switch the baudrate of a slave.
For details see chapter 9.1.

3 Data Header of variable data respond 4 Variable Data Structure

4.1 Slave to master (answer) direction

The CI-Field codes 72h/(76h) are used to indicate the variable data structure in long frames (RSP_UD). Figure 2 1 shows the way this data is represented:

Data Header(Req.)

Variable Data Blocks (Records)

MDH(opt)O

Opt.Mfg.specific data Opt)

12 Byte

variable number

1 Byte

variable number

Fig. 12 Variable Data Structure in Answer Direction

3.14.1.1 Structure of Data Header

The first twelve bytes of the user data consist of a block with a fixed length and structure (see fig. 32).

Ident. Nr.

Manufr.

Version

Device typeMedium

Access No.

Status

Signature

4 Byte

2 Byte

1 Byte

1 Byte

1 Byte

1 Byte

2 Byte

Fig. 23 Fixed Data HeaderBlock

3.24.1.2 Identification number

The Identification Number is either a fixed fabrication number or a customer number changable by the customer, coded with 8 BCD packed digits (4 Byte), and which thus runs from 00000000 to 99999999. It can be preset at fabrication time with a unique number, but could be changeable afterwards, especially if in addition an unique and not changeable fabrication number (DIF = $0C, VIF = $78, see chapter 6.7.3) is provided.

34.1.3 Manufacturer identification

The field manufacturer is coded unsigned binary with 2 bytes. This manufacturer ID is calculated from the ASCII code of EN 61107 manufacturer ID (three uppercase letters) with the following formula:

IEC 870 Man. ID = [ASCII(1st letter) - 64] · 32 · 32

+ [ASCII(2nd letter) - 64] · 32

+ [ASCII(3rd letter) - 64]

Note that currently the flag association administers these three letter manufacturers ID of EN61107. For details see appendix X.

34.1.4 Version identification

The field version specifies the generation or version of the meter and depends on the manufacturer. It can be used to make sure, that within each version number the identification # is unique.

34.1.5 Medium Device type identification

The medium device byte is coded as follows:

Device type (previously called medium)Medium

Code bin.

Bit 7 .. 0

Code hex.

Other

0000 0000

00

Oil

0000 0001

01

Electricity

0000 0010

02

Gas

0000 0011

03

Heat (Volume measured at return temperature: outlet)

0000 0100

04

Steam

0000 0101

05

WarmHot Water (30°C-90°C)

0000 0110

06

Water

0000 0111

07

Heat Cost Allocator.

0000 1000

08

Compressed Air

0000 1001

09

Cooling load meter (Volume measured at return temperature: outlet)

0000 1010

0A

Cooling load meter (Volume measured at flow temperature: inlet)

0000 1011

0B

Heat (Volume measured at flow temperature: inlet)

0000 1100

0C

Heat / Cooling load meter

0000 1101

OD

Bus / System component

0000 1110

0E

Unknown Medium

0000 1111

0F

Reserved

..........

10 to 145

Hot water (>=90°C)

0001 0101

15

Cold Water

0001 0110

16

Dual Water

0001 0111

17

Pressure

0001 1000

18

A/D Converter

0001 1001

19

Reserved

..........

20 to FF

Table 3 Device type identification

Note that this table has been expanded with optional elements from the original standard.

3.4.1.6 Access number

The Access Number has unsigned binary coding, and is increased (modulo 256) by one before or after each RSP_UD from the slave. Since it can also be used to enable private end users to detect an unwanted overfrequently readout of its consumption meters, it should not be resettable by any bus communication.

34.1.7 Status byte

Bit

Meaning with Bit set

Significance with Bit not set

0,1

See table 5Fig.4

See table 5Fig.4

2

Power low

Not power low

3

Permanent error

No permanent error

4

Temporary error

No temporary error

5

Specific to manufacturer

Specific to manufacturer

6

Specific to manufacturer

Specific to manufacturer

7

Specific to manufacturer

Specific to manufacturer

Table 4 Fig. 3 Coding of the Status Field

Status bit 1 bit 0

Application status

0 0

No Error

0 1

Application Busy

1 0

Any Application Error

1 1

Reserved

Table 5 Fig. 4 Application Errors coded with the Status-Field

Note that more detailed error signalling can be provided by application telegrams starting with CI=$70 and/or using data records signalling even more detailed error information.

3.8 Signature field

The Signature is reserved for optional encryptation of the application data. If no encryptation is used its value shall be 00 00 h.

3.8.1 Functions

Data privacy for consumption meters values

Detecting simulated meter transmission

Preventing later playback of old meter values

3.8.2 Structure of encrypted telegrams

a) The first 12-byte block containing the ID-number,

the manufacturer etc. is always unencrypted.

The last word of this block is the signature word.

If the following data are unencrypted, this

signature word contains a zero.

b) If the transmission contains encrypted data,

the high byte of this signature word contains a code for

the encryptation method. The code 0 signals no

encryptation. Currently only the encryptation codes 2 or 3

(see below) are defined. The other codes are

reserved. The number of encrypted bytes is contained

in the low byte of the signature word.

The content of this signature word is currently defined

as zero, corresponding consistently to no encrypted data.

c) The encrypted data follow directly after the

signature word, thus forming the beginning of the

DIF/VIF-structured part of the telegram.

 

3.8.3 Partial Encryption

a) If the number of encrypted bytes is less than the

remaining data of the telegram, unencrypted data may

follow after the encrypted data. They must start at a

record boundary, i.e. the first byte after the encrypted

data will be interpreted as a DIF.

b) If a partially encrypted telegram must contain encrypted

manufacturer specific data a record with a suitable length

DIF (possibly a variable length string DIF) and a VIF=

$7F (manufacturer specific data record) must be used

instead of the usual MDH-DIF=$0F. This is required to

enable after decryptation standard DIF/VIF-decoding of a previously partially encrypted telegram containing

encrypted manufacturer specific data .

3.8.4 Encryptation methods

a) Encryptation according to the DES (data encryptation

standard) as described in ANSI X3.92-1981

b) Cipher Block Chaining (CBC)-method as described in

ANSI X3.106-1983 with an initial initialization vector

of zero: (Encryptation Method Code=2). In this case

the data records should contain the current date

before the meter reading.

Note that in this case the data after the date record,

i.e.especially the encrypted meter reading data

change once per day even if their data content itself is

constant. This prevents an undetectable later playback of

stored encrypted meter readings by a hacker.

c) The "Initialization Vector IV" with length 64 bits of this

standard may alternatively be defined by the the first 6

bytes of the identification header in mode 1 sequence,

i.e. identification number in in the lowest 4 bytes

followed by the manufacturer ID in the two next higher

bytes and finally by the current date coded as in record

structure "G" for the two highest bytes.

In this case the encryptation method is coded as "3".

Note that in this case all encrypted data change once

per day even if the data content itself is constant.

This prevents an undetectable later playback of any

stored encrypted data by a hacker.

 

d) To simplify the verification of correct decoding and to

prevent an undetected change in the identification of the

not encrypted header, the encrypted part of the telegram

must contain at least together with the appropriate application

layer coding (DIF and VIF) again the same identification

number as in the unencrypted header.

e) Due to the mathematical nature of the DES-algorithm

the encrypted length contained in the low byte of the

signature word must be an integer multiple of 8 if

the high byte signals DES-encryptation.

Unused bytes in the last 8-byte block must be filled

with appropriatly structured dummy data records to

achieve the required record boundary at the end of the

encrypted data. One or several bytes containing the filler

DIF=$2F are suggested to fill such gaps.

f) The application of certain encryptation methods might be

prohibited by local laws.

 

4.1.8 Signature field

The Signature remains reserved for future encryptation applications, and until then is allocated the value 00 00 h.

Variable Data Blocks (Records)

MDH(opt)O

Opt.Mfg.specific data Opt)

variable number

1 Byte

variable number

Fig. 5 Variable Data Structure in Answer Direction

Note that this structure is identical to the slave to master direction with the exception of the fixed header which is omitted in this direction.

4.3 Variable Data Blocks (Records)

The data, together with information regarding coding, length and the type of data is transmitted in data records in arbitrary sequence. As many records can be transferred as there is room for within the maximum total data length of 234255 Bytes, and taking account of the C, A, and CI fields, and the data header. This limits the total telegram length to 255 bytes. This restriction is required to enable gateways to other link- and application layers. e upper limit for characters in the variable data blocks is thus 240 byte. A maximum total telegram length of 255 bytes (234 bytes for variable data blocks) is recommended to simplify gateways and the integration in other link layers . The manufacturer data header (MDH) is made up by the character 0Fh or 1Fh and indicates the beginning of the manufacturer specific part of the user data and should be omitted, if there are no manufacturer specific data.

DIF

DIFE

VIF

VIFE

Data

1 Byte

0-10 (1 Byte each)

1 Byte

0-10 (1 Byte each)

0-N Byte

Data Information Block DIB

Value Information Block VIB

 

Data Record Header DRH

 

Fig. 46 Structure of a Data Record (transmitted from left to right)

Each data record contains one value (data) with its description (DRH)as shown in figure 20, a data record, which consists of a data record header (DRH) and the actual data. The DRH in turn consists of the DIB (data information block) to describe the length, type and coding of the data, and the VIB (value information block) to give the value of the unit and the multiplier.

4.3.1 Data Information Block (DIB)

The DIB contains at least one byte (DIF, data information field), and can be extended by a maximum of ten DIFE's (data information field extensions).

4.3.2 Data Information Field (DIF)

The following information is contained in a DIF:

Bit 7

6

5

4

3

2

1

0

Extension

Bit

LSB of storage number

Function Field

Data Field :

Length and coding of data

Fig. 57 Coding of the Data Information Field (DIF)

4.3.3 Data Field

The data field shows how the data from the master must be interpreted in respect of length and coding. The following table contains the possible coding of the data field:

Length in Bit

Code

Meaning

Code

Meaning

0

0000

No data

1000

Selection for Readout

8

0001

8 Bit Integer

1001

2 digit BCD

16

0010

16 Bit Integer

1010

4 digit BCD

24

0011

24 Bit Integer

1011

6 digit BCD

32

0100

32 Bit Integer

1100

8 digit BCD

32 / N

0101

32 Bit Real

1101

variable length

48

0110

48 Bit Integer

1110

12 digit BCD

64

0111

64 Bit Integer

1111

Special Functions

Table 46 Coding of the data field

Note that this table has been expanded with optional elements from the original standard.

For a detailed description of data types refer to appendix A8.2 " Coding of data records"
(e.g. BCD = Type A, Integer = Type B, Real = Type H).

 

Variable Length:

With data field = `1101b` several data types with variable length can be used. The length of the data is given after the DRH with the first byte of real data, which is here called LVAR (e.g. LVAR = 02h: ASCII string with two characters follows).

LVAR = 00h .. BFh : Text string according to ISI/IEC 646 with LVAR characters

LVAR = C0h .. C9h : positive BCD number with (LVAR - C0h) · 2 digits

LVAR = D0h .. D9H : negative BCD number with (LVAR - D0h) · 2 digits

LVAR = F8h : floating point number according to IEEE 754

Others LVAR values : Reserved

Like all multibyte fields in mode 1 the last character and in mode 2 the first character is transmitted first.

Special Functions (data field = 1111b):

DIF

Function

0Fh

Start of manufacturer specific data structures to end of user data

1Fh

Same meaning as DIF = 0Fh + More records follow in next telegram

2Fh

Idle Filler (not to be interpreted), following byte = DIF of next record

3Fh..6Fh

Reserved

7Fh

Global readout request (all storage#, units, tariffs, function fields)

Table 7: DIF-coding for special functions

Note that this table has been expanded with optional elements from the original standard.

If data follows after DIF=$0F or $1F these are manufacturer specific unstructured data. The number of bytes in these manufacturer specific data can be calculated from the link layer information on the total length of the application layer telegram. The DIF 1Fh signals a request from the slave to the master to readout the slave once again. The master must readout the slave until there is no DIF=1Fh inside the respond telegram (multi telegram readout) or use an application reset.

 

4.3.4 Function field

The function field gives the type of data as follows:

Code

Description

Code

Description

00b

Instantaneous value

01b

Maximum value

10b

Minimum value

11b

Value during error state

Table 8: Function Field

4.3.5 Storage number

The Bit 6 of the DIF serves as the LSB of the storage number of the data concerned, and the slave can in this way indicate and transmit various stored metering values or historical values of metering data. This bit is the least significant bit of the storage number and allows therefore the storage numbers 0 and 1 to be coded. If storage numbers higher than "1" are needed, following (optional) DIFEīs contain the higher bits. The storage number 0 signals an actual value. Note that a each storage number is associated with a given timepoint. So all data records with the same storage number refer to the value of the associated variable at this (common) timepoint for this storage number. It is recommended, that a time/date record with this storage number is included somewhere to signal this timepoint. Normally (but not necessarily) higher storage numbers indicate an older timepoint. A sequential block of storage numbers can be associated with a sequence of equidistantly spaced time points (profile). Such a block can be described by its starting time, by the time spacing, by the first storage number of such a block and by the length of such a block. The coding for such a block description in contrast to an individual time/date record for each individula storage number is given in the appendix.

4.3.6 Extension Bit

The extension bit (MSB) signals that more detailed or extended descriptions (data field extension=DIFE)-bytes follow.

4.3.7 Data field extension byte(s) (DIFE)

Each DIFE (maximum ten) contains again an extension bit to show whether a further DIFE is being sent. Besides giving the next most significant bits of the storage number, DIFEīs allow the transmission of informations about the tariff and the subunit of the device from which the data come. In this way, exactly as with the storage number, the next most significant bit or bits will be transmitted. The figure 8 which follows shows the structure of a DIFE:

Bit 7

6

5

4

3

2

1

0

Extension Bit

(Device) Unit

Tariff

Storage Number

Fig. 58 Coding of the Data Information Field Extension (DIFE)

With the maximum of ten DIFEīs which are provided, there are 41 bits for the storage number, 20 bits for the tariff, and 10 bits for the subunit of the meter. There is no application conceivable in which this immense number of bits could all be used.

4.3.8 Tariff information

For each (unique) value type designation given by the following value information block (VIB) at each unique time point (given by the storage number) of each unique function (given by the function field) there might exist still various different data, measured or accumulated under different conditions. Such conditions could be time of day, various value ranges of the variable (i.e. separate storage of positive accumulatad values and negative accumulated values) itself or of other signals or variables or various averaging durations. Such variables which could not be distinguished otherwise are made different by assigning them different values of the tariff variable in their data information block. Note that this includes but is not necessarily restricted to various tariffs in a monetary sense. It is at the distinction of the manufacturer to describe for each tariff (except 0) what is different for each tariff number. Again as with the storage numbers all variables with the same tariff information share the same tariff associating condition.

4.93.8 Subunit information

A slave component may consist of several functionally and logically independent subunits of the same or of different functionallity. Such a device may either use several different primary and/or secondary adresses. Such it is from a link layer and an application layer view just several independent devices which share a common physical layer interface. This is recommended for devices which represent a physical collection of several truely independent (often similar or idential) devices. For devices which share common information and values and have logical connections an approach with a common link layer (i.e.a single address) is reccomended. The various subunits can include their specific information into a common telegram and have them differentiated by the individual subunit number in the subunit-datafield of their records.

54.4 Value Information Block (VIB)

After a DIF (with the the exception of $xF) or a DIFE without a set extension bit there follows the VIB (value information block). This consists at least of the VIF (value information field) and can be expanded with a maximum of 10 extensions (VIFE). The VIF and also the VIFE's show with a set MSB that a VIFE will follow. In the value information field VIF the other seven bits give the unit and the multiplier of the transmitted value.

Bit 7

6

5

4

3

2

1

0

Extension Bit

Unit and multiplier (value)

Fig. 69 Coding of the Value Information Field (VIF)

There are five types of coding depending on the VIF:

a)1. Primary VIF: E000 0000b .. E111 1011b

The unit and multiplier is taken from the table for primary VIF (Table 9chapter 8.4.3).

b)2. Plain-text VIF: E111 1100b

In case of VIF = 7Ch / FCh the true VIF is represented by the following ASCII string with the length given in the first byte. Please note that the byte order of the characters after the length byte depends on the used byte sequence. Since only the "LSB first mode" (M=1) of multibyte data transmission is recommended, the rightmost character is transmitted first. This plain text VIF allows the user to code units that are not included in the VIF tables..

c)3. Linear VIF-Extension: FDh and FBh

In case of VIF = FDh and VIF = FBh the true VIF is given by the next byte (i.e. the first VIFE) and the coding is taken from the tables 11 respectively table 12 for secondary VIF (chapter 8.4.4). This extends the available VIFīs by another 256256 codes.

d)4. Any VIF: 7Eh / FEh

This VIF-Code can be used in direction master to slave for readout selection of all VIFīs. See chapter 6.4.3.

e)5. Manufacturer specific: 7Fh / FFh

In this case the remainder of this data record including VIFEīs has manufacturer specific coding.

 

5.1 Primary VIFīs (main table)

The first section of the main table contains integral values, the second typically averaged values, the third typically instantaneous values and the fourth block contains parameters (E: extension bit).

4.4.1 Primary VIFīs (main table)

Coding

Description

Range Coding

Range

E000 0nnn

Energy

10(nnn-3) Wh

0.001Wh to 10000Wh

E000 1nnn

Energy

10(nnn) J

0.001kJ to 10000kJ

E001 0nnn

Volume

10(nnn-6) m3

0.001l to 10000l

E001 1nnn

Mass

10(nnn-3) kg

0.001kg to 10000kg

E010 00nn

On Time

nn = 00 seconds

nn = 01 minutes

nn = 10 hours

nn = 11 days

E010 01nn

Operating Time

coded like OnTime

E010 1nnn

Power

10(nnn-3) W

0.001W to 10000W

E011 0nnn

Power

10(nnn) J/h

0.001kJ/h to 10000kJ/h

E011 1nnn

Volume Flow

10(nnn-6) m3/h

0.001l/h to 10000l/h

E100 0nnn

Volume Flow ext.

10(nnn-7) m3/min

0.0001l/min to 1000l/min

E100 1nnn

Volume Flow ext.

10(nnn-9) m3/s

0.001ml/s to 10000ml/s

E101 0nnn

Mass flow

10(nnn-3) kg/h

0.001kg/h to 10000kg/h

E101 10nn

Flow Temperature

10(nn-3) °C

0.001°C to 1°C

E101 11nn

Return Temperature

10(nn-3) °C

0.001°C to 1°C

E110 00nn

Temperature Difference

10(nn-3) K

1mK to 1000mK

E110 01nn

External Temperature

10(nn-3) °C

0.001°C to 1°C

E110 10nn

Pressure

10(nn-3) bar

1mbar to 1000mbar

E110 110n

Time Point

n = 0 date

n = 1 time & date

data type G

data type F

data type F

E110 1110

Units for H.C.A.

dimensionless

E110 1111

Reserved

E111 00nn

Averaging Duration

coded like OnTime

E111 01nn

Actuality Duration

coded like OnTime

E111 1000

Fabrication No

E111 1001

(Enhanced) Identification

see appendix E2chapter 6.4.2 §

E111 1010

Bus Address

data type C (x=8)

Table 9: Primary VIF-codes

Note that this table has been expanded with optional elements from the original standard.

54.4.2 VIF-Codes for special purposes:

Coding

Description

Purpose

1111 1011

Extension of VIF-codes

true VIF is given in the first VIFE and is coded using

table 108.4.4 b) (128 new VIF-Codes)

E111 1100

VIF in following string

(length in first byte)

allows user definable VIFīs (in plain ASCII-String) *

1111 1101

Extension of VIF-codes

true VIF is given in the first VIFE and is coded using

table 118.4.4 a) (128 new VIF-Codes)

E111 1110

Any VIF

used for readout selection of all VIFīs

(see chapter 9.26.4.3 )

E111 1111

Manufacturer Specific

VIFEīs and data of this block are manufacturer specific

Table 10: Special VIF-Codes

Note that this table has been expanded with optional elements from the original standard.

Note:

* Coding the VIF in an ASCII-String in combination with the data in an ASCII-String (datafield in DIF = 1101 b) allows the representation of data in a free user defined form.

54.4.3 MainFirst VIFE-Code Extension table (following VIF=$FD for primary VIF)

Coding

Description

Group

E000 00nn

Credit of 10nn-3 of the nominal local legal currency units

Currency Units

E000 01nn

Debit of 10nn-3 of the nominal local legal currency units

 

E000 1000

Access Number (transmission count)

 

E000 1001

Device typeMedium (as in fixed header)

 

E000 1010

Manufacturer (as in fixed header)

 

E000 1011

Parameter set identification

Enhanced Identification

E000 1100

Model / Version

 

E000 1101

Hardware version #

 

E000 1110

Firmware version #

 

E000 1111

Software version #

 

E001 0000

Customer location

 

E001 0001

Customer

 

E001 0010

Access Code User

 

E001 0011

Access Code Operator

Implementation of all

E001 0100

Access Code System Operator

TC294 WG1 requirements

E001 0101

Access Code Developer

(improved selection ..)

E001 0110

Password

 

E001 0111

Error flags (binary) (Device type specific)

 

E001 1000

Error mask

 

E001 1001

Reserved

 

E001 1010

Digital Output (binary)

 

E001 1011

Digital Input (binary)

 

E001 1100

Baudrate [Baud]

 

E001 1101

response delay time [bittimes]

 

E001 1110

Retry

 

E001 1111

Reserved

 

E010 0000

First storage # for cyclic storage

 

E010 0001

Last storage # for cyclic storage

 

E010 0010

Size of storage block

 

E010 0011

Reserved

 

E010 01nn

Storage interval [sec(s)..day(s)] Œ

Enhanced storage

E010 1000

Storage interval month(s)

management

E010 1001

Storage interval year(s)

 

E010 1010

Reserved

 

E010 1011

Reserved

 

E010 11nn

Duration since last readout [sec(s)..day(s)] Œ

 

E011 0000

Start (date/time) of tariff 

 

E011 00nn

Duration of tariff (nn=01 ..11: min to days)

 

E011 01nn

Period of tariff [sec(s) to day(s)] Œ

 

E011 1000

Period of tariff months(s)

Enhanced tariff

E011 1001

Period of tariff year(s)

management

E011 1010

dimensionless / no VIF

 

E011 1011

Reserved

 

E011 11xx

Reserved

 

E100 nnnn

10nnnn-9 Volts

electrical units

E101 nnnn

10nnnn-12 A

 

 

 

 

E110 0000

Reset counter

 

E110 0001

Cumulation counter

 

E110 0010

Control signal

 

E110 0011

Day of week

 

E110 0100

Week number

 

E110 0101

Time point of day change

 

E110 0110

State of parameter activation

 

E110 0111

Special supplier information

 

E110 10pp

Duration since last cumulation [hour(s)..years(s)]Ž

 

E110 11pp

Operating time battery

[hour(s)..years(s)]Ž

 

E111 0000

Date and time of battery change

 

E111 0001

to

E111 1111

Reserved

 

Table 11: Main VIFE-code extension table

Note that this optional table has been added to the original standard.

Notes:

Œ nn = 00 second(s)

01 minute(s)

10 hour(s)

11 day(s)

 The information about usage of data type F (date and time) or data type G (date) can be derived from the datafield (0010b: type G / 0100: type F).

Ž pp = 00 hour(s)

01 day(s)

10 month(s)

11 year(s)

 

54.4.4 Alternate VIFE-Code Extension table (following VIF=$FB for primary VIF)

Coding

Description

Range Coding

Range

E000 000n

Energy

10(n-1) MWh

0.1MWh to 1MWh

E000 001n

Reserved

   

E000 01nn

Reserved

   

E000 100n

Energy

10(n-1) GJ

0.1GJ to 1GJ

E000 101n

Reserved

   

E000 11nn

Reserved

   

E001 000n

Volume

10(n+2)

 

E001 001n

Reserved

   

E001 01nn

Reserved

   

E001 100n

Mass

10(n+2) t

100t to 1000t

E001 1010-E010 0000

Reserved

   

E010 0001

Volume

0,1 feet^3

 

E010 0010

Volume

0,1 am.gallon

 

E010 0011

Volume

1 am.gallon

 

E010 0100

Volume flow

0,001 am.gallon/min

 

E010 0101

Volume flow

1 am.gallon/min

 

E010 0110

Volume flow

1 am.gallon/h

 

E010 0111

Reserved

   

E010 100n

Power

10(n-1) MW

0.1MW to 1MW

E010 101n

Reserved

   

E010 11nn

Reserved

   

E011 000n

Power

10(n-1) GJ/h

0.1GJ/hto 1GJ/h

E011 0010-E101 0111

Reserved

   

E101 10nn

Flow Temperature

10(nn-3) °F

0.001°F to 1°F

E101 11nn

Return Temperature

10(nn-3) °F

0.001°F to 1°F

E110 00nn

Temperature Differ.

10(nn-3) °F

0.001°F to 1°F

E110 01nn

Flow Temperature

10(nn-3) °F

0.001°F to 1°F

E110 1nnn

Reserved

   

E111 00nn

Cold/Warm Temp. Lim.

10(nn-3) °F

0.001°F to 1°F

E111 01nn

Cold/Warm Temp. Lim.

10(nn-3) °C

0.001°C to 1°C

E111 1nnn

Cum.Count Max.power

10(nnn-3) W

0.001W to 10000W

Table 12: Alternate extended VIF-code Table

Note that this optional table has been added to the original standard.

54.4.5 Combinable (Orthogonal) VIFE-Code Extension table (Following primary VIF)

VIFE-Code

Description

E00x xxxx

Reserved for object actions (master to slave): see chapter 6.3 and table 16table on page 75

or for error codes (slave to master): see chapter 7 and table 17table on page 74

E010 0000

per second

E010 0001

per minute

E010 0010

per hour

E010 0011

per day

E010 0100

per week

E010 0101

per month

E010 0110

per year

E010 0111

per revolution / measurement

E010 100p

increment per input pulse on input channel #p

E010 101p

increment per output pulse on output channel #p

E010 1100

per liter

E010 1101

per m3

E010 1110

per kg

E010 1111

per K (Kelvin)

E011 0000

per kWh

E011 0001

per GJ

E011 0010

per kW

E011 0011

per (K*l) (Kelvin*liter)

E011 0100

per V (Volt)

E011 0101

per A (Ampere)

E011 0110

multiplied by sek

E011 0111

multiplied by sek / V

E011 1000

multiplied by sek / A

E011 1001

start date(/time) of Œ 

E011 1010

VIF contains uncorrected unit instead of corrected unit

E011 1011

Accumulation only if positive contributions

E011 1100

Accumulation of abs value only if negative contributions

E011 1101 to

E011 1111

Reserved

VIFE-Code

Description

E100 u000

u=1: upper, u=0: lower limit value

E100 u001

# of exceeds of lower u=0) / upper (U=1) limit

E100 uf1b

Date (/time) of: b=0: begin, b=1: end of, f=0: first, f=1: last,

 u=0: lower, u=1: upper limit exceed

E101 ufnn

Duration of limit exceed (u,f: as above, nn=duration)

E110 0fnn

Duration of Œ (f: as above, nn=duration)

E110 1x0x

Reserved

E110 1f1b

Date (/time) of Œ  (f,b: as above)

E111 0nnn

Multiplicative correction factor: 10nnn-6

E111 10nn

Additive correction constant: 10nn-3 · unit of VIF (offset)

E111 1100

Reserved

E111 1101

Multiplicative correction factor for value (not unit): 103

E111 1110

future value

E111 1111

next VIFE's and data of this block are maufacturer specific

Table 13: Combinable (orthogonal) VIFE-Table

Note that this optional table has been added to the original standard.

 

Notes:

Œ "Date(/time) of" or "Duration of" relates to the information which the whole data record header contains.

 The information about usage of data type F (date and time) or data type G (date) can be derived from the datafield (0010b: type G / 0100: type F).

65 Application Layer Status and error reporting

The data link layer reports only communication errors by means of omittingleaving out the acknowledgement $E5 or a via a negative acknowledgement. It is not allowed to report errors of the application layer (which can occur for example in data writing) via the link layer. The slave can transmit an $E5 after a SND_UD to indicate that it has received the telegram, but canīt respond with data. There are three different techniques for reporting application errors:

65.1 Status Field

One possible solution is to use the reserved 2 lowest bits of the Status field in the variable data structure for the application layer status (see Table 6).:

 

Fig. 5 Application Errors coded with the Status-Field

65.2 General Application Layer Errors

For reporting general application errors a slave can use a RSP_UD telegram with CI=$70 and zero, one or several data bytes, which then describes the type of error:

68h

04h

04h

68h

08h

PAdr

70h

DATA

CS

16h

Fig. 6 Telegram for reporting general application errors

The following values for DATA are defined:

0

Unspecified error: also if data field is missing

1

Unimplemented CI-Field

2

Buffer too long, truncated

3

Too many records

4

Premature end of record

5

More than 10 DIFEīs

6

More than 10 VIFEīs

7

Reserved

8

Application too busy for handling readout request

9

Too many readouts (for slaves with limited readouts per time)

10..255

Reserved

Table 5 15 Codes for general application errors

Note that this optional table has been added to the original standard.

65.3 Record Errors

To report errors belonging to a special record the slave can use this data record header with a VIFE containing one of the following values to code the type of application error, which has been occured.

VIFE-Code

Type of Record Error

Error Group

E000 0000

None

 

E000 0001

Too many DIFEīs

 

E000 0010

Storage number not implemented

 

E000 0011

Unit number not implemented

 

E000 0100

Tariff number not implemented

DIF Errors

E000 0101

Function not implemented

 

E000 0110

Data class not implemented

 

E000 0111

Data size not implemented

 

E000 1000 to

E000 1010

Reserved

 

E000 1011

Too many VIFEīs

 

E000 1100

Illegal VIF-Group

 

E000 1101

Illegal VIF-Exponent

VIF Errors

E000 1110

VIF/DIF mismatch

 

E000 1111

Unimplemented action

 

E001 0000 to

E001 0100

Reserved

 

E001 0101

No data available (undefined value)

 

E001 0110

Data overflow

 

E001 0111

Data underflow

 

E001 1000

Data error

Data Errors

E001 1001 to

E001 1011

Reserved

 

E001 1100

Premature end of record

 

E001 1101

to

E001 1111

Reserved

Other Errors

Table 6 16: Codes for record errors (E = extension bit)

Note that this optional table has been added to the original standard.

In case of record errors the data maybe invalid. The slave has some options to transmit the data:

· datafield = 0000b: no data

· datafield = 0000b: no data and idle filler (DIF=$2F): fill telegram record up to the normal length

· other datafield: dummy data of correct length

· other datafield: unsafe or estimated data

76 Generalized Object Layer

The fundamental idea of an object is the encapsulation of data and methods or actions for the data. In case of writing data to a slave the master software can pack data and information about the action, which the slave shall do with this data, in one data record. This variable data record with actions is now called an object. Following any VIF including a VIF=$FD or VIF=$FB with the true value information in the first VIFE another (usually the last) VIFE can be added which contains a code signalling object actions according to the following table.

Action: (E: extension bit)

VIFE-Code binary

Action

Explanation

E000 0000

Write (Replace)

replace old with new data

E000 0001

Add Value

add data to old data

E000 0010

Subtract Value

subtract data from old data

E000 0011

OR (Set Bits)

data OR old data

E000 0100

AND

data AND old data

E000 0101

XOR (Toggle Bits)

data XOR old data

E000 0110

AND NOT (Clear Bits)

NOT data AND old data

E000 0111

Clear

set data to zero

E000 1000

Add Entry

create a new data record

E000 1001

Delete Entry

delete an existing data record

E000 1010

Reserved

 

E000 1011

Freeze Data

freeze data to storage no.

E000 1100

Add to Readout-List

add data record to RSP_UD

E000 1101

Delete from Readout-List

delete data record from RSP_UD

E000 111x

Reserved

 

E001 xxxx

Reserved

 

Fig. 7 Table 17: Action Codes for the Generalized Object layer (Master to Slave)

Note that this optional table has been added to the original standard.

Note:

The object action "write / replace" (VIFE = E000 0000) is the default and is assumed if there is no VIFE with an object action for this record.

87 Manufacturer Specific unstructured Data Block

The MDH consists of the character 0Fh or 1Fh (DIF = 0Fh or 1Fh) and indicates that all following data are manufacturer specific. When the total number of bytes given from the link/network layers and the number of record-structured bytes and the length of the fixed header is known, the number of remeining unstructured manufacturer specific bytes can be calculated.

Note that stuctured manufacturer specific data (i.e. those with a known data structure including variable length binary or ASCII but with a manufacturer specific meaning or unit) can be described using normal data records with a value information field of VIF=E1111111b.

In case of MDH = 1Fh the slave signals to the master that it wants to be readout once again (multitelegram readouts). The master must readout the data until there is no MDH = 1Fh in the respond telegram.

98 Management of lower layers

Because changing of parameters like baudrate and address by higher layers is not allowed in the ISO-OSI-Model, a Management Layer beside and above the seven OSI-Layers is defined:

 

Management Layer

Application Layer

 

Presentation Layer

 

Session Layer

 

Transport Layer

 

Network Layer (if address = 253)

Address 253 / Enable Disable CI=$52/$56

Data Link Layer

 

Physical Layer

Address 254 (255)/251

Fig. 8 Management-Layer of the M-Bus

So the address 254 and perhaps 255 can be used also for managing the physical layer of the bus and the adress 251 is reserved for managing the (primary) M-Bus level converter/bridge and the address 253 (selection) for network layer (see chapter 7), which is only used in certain cases. With such a managment addresses and or CI-fields we can directly manage each OSI-layer to implement features, which are beyond the elementary OSI-Model.

98.1 Switching Baudrate

All slaves must be able to communicate with the master using the minimum transmission speed of 300 baud. , after reception of a break signal and after each bus power fail.Split baudrates between transmit and receive are not allowed, but there can be devices with different baudrates on the bus.

In point to point connections the slave is set to another baudrate by a Control Frame (SND_UD with L-Field = 3) with address FEh and one of the following CI-Field codes: Note that for safety reasons a baudrate switch command to the (unacknowledged) broadcast adress 255 is not recommended.

A complete bus can be switched to another baudrate via the broadcast adress $FF.

 

CI-Field

B8h

B9h

BAh

BBh

BCh

BDh

Beh

BFh

Baud

300

600

1200

2400

4800

9600

19200

38400

Note

1

1

1

1

1

Fig. 9 CI-Field-Codes for Baudrate Switching

Note that this optional figure has been added to the original standard.

Notes:

1) These baudrates are not recommended only by agreement with operator.

The slave always confirms the correctly received telegram by transmitting an E5h with the old baudrate and uses the new baudrate from now on, if he is capable of this. Otherwise the slave stays at ists previous baudrate after the $E5 acknowledge. To make sure that a slave without autospeed detect has properly switched to the new baudrate and that it can communicate properly at the new baudrate in its segment it is required that after a baudrate switch to a baudrate other than 300 Baud the master attempts imediately (<2min) after the baudrate switch command a communication. If (even after the appropriate number of retries) this is not acknowledged by the slave, the master shall issue a baudrate set command (at the attempted new baudrate) back to the previous baudrate. If a slave without autospeed detect does not receive a valid communication at the new baudrate within 2-10 minutes of the baudrate switch command the slave must fall back to its previous baudrate. This is required individually and sequentially for each adressable slave.

The master must know the highest available baudrate on the bus to forbid the user switching to a transmission speed, which is not available on the bus. Otherwise the slave would never answer again. In this case intelligent primary level converters or bridges (with special address = 251) can generate a break signal on the bus if they receive a SND_UD-telegram with a CI-field of $B0.

For compatibility with older slaves with fallback to 300 baud the master should also attempt a communication at 300 baud if the slave does not answer at its last baudrate.

98.2 Selection and Secondary Addressing (optional network layer)

The network layer takes care of choosing the best transmission route between the communication parties in a network. We define that the network layer in the M-Bus protocol "connects" a slave with a certain secondary address to the bus and and associates it with the primary address of 253 ($FD). So the maximum number of 250 addresses (primary) is extended by the network layer associating a selected slave to this address 253. The network layer is only enabled by a SND_UD with CI_Field $52 / $56 to address 253.

When addressing in the data link layer with the help of the A-Field, the problem of the address allocation could arise. The addresses are normally set to a value of 0 by the manufacturer of the meters, in order to designate them as unconfigured slaves. A very laborious method of address allocation consists of setting the addresses when installing the slaves, for example with DIP switches. A further method of address allocation is to determine the bus addresses when connecting the equipments to the bus with the master software. This sends a command for address allocation (see 6.4.2Appendix E2) to the address 0. In this case the slaves must however all be successively connected to the bus, which very much gets in the way of a simple installation procedure.

When however addressing in the network layer these disadvantages are avoided and the address region is essentially extended beyond the number of 250 with primary addressing (A-Field). The addressing of the slaves takes place with secondary addressing with the help of the following so-called selection:

68h

0Bh

0Bh

68h

53h

FDh

52h

ID1-4

Man 1-2

Gen

MedDev

CS

16h

Fig. 10 Structure of a telegram for selecting a slave (mode 1)

The master sends a SND_UD with the control information 52h (Mode 1) or 56h (Mode 2 ) to the address 253 (FDh) and fills the specific meter secondary address (identification number, manufacturer, version and device typemedium) with the values of the slave which is to be addressed. After the reception of the address FDh the selection mode is entered. If then the proper CI-selection code (normally CI=52h, i.e. mode 1) is received the internal selection bit is set otherwise it is reset. If further data bytes follow they are compared with the corresponding internal addresses respective values of the meter. If they disagree, the selection bit is cleared otherwise it is left unchanged. Thus "selecting" a meter with only a proper CI-field and no further data will select all meters on the bus capable of secondary addressing. A set selection bit means that this slave can be addressed (e.g. REQ_UD) with the bus address FDh and in this example will reply with RSP_UD. In other words the network layer has associated this slave with the address FDh.

During selection individual positions of the secondary addresses can be occupied with wildcards (Fh). Such a Wildcard means that this position will not be taken account of during selection, and that the selection will be limited to specific positions, in order to address complete groups of slaves (Multicasting). In the identification number each individual digit can be wildcarded by a wildcard nibble Fh while the fields for manufacturer, version and device typemedium can be wildcarded by a wildcard byte FFh.

The state of the selection remains unchanged until the slave is deselected with a selection command (as described above) with non-matching secondary addresses, or a SND_NKE to address 253. The slave, which uses mode 1 for multibyte records, will be selected by a telegram with the CI-Field 52h and the right secondary address, but it will be deselected by a telegram with the CI-Field 56h and any secondary address.

A sSlave with implemented primary and secondary addressing should also answer telegrams to his primary address. A sSlave with only secondary addressing (i.e. internal primary adress=253) should occupy the address field in the RSP_UD telegram with $FD to signal that it will not participate in primary addressing.

98.3 Generalized Selection Procedure

For including new or restructed identification parameters into a selection procedure an enhanced definition of the selection telegram (CI=$52/$56) can be used:

After the 8 byte of the fixed selection header may also follow standard records with data. In this case only those meters will be selected, where in addition to the fixed header all record data agree. In most but not all cases this means that the DIF and parts of the VIF (not exponent) must match. Again wildcard rules apply to the record data (digit wildcard for BCD-coded data and byte wildcard for binary or string data).

With this generalized selection it will be possible to select slaves using e.g. additional fabrication number, longer identification numbers, customer, customer location and more information. Two useful examples from the primary table for VIFīs are the "Fabrication No." and "Customer name". For inclusion of the fabrication number in the selection process

after the field "device type" the 8-digit BCD-fabrication number follow. Parts of the fabrication number (Fab1..Fab4) can be occupied with wildcards (Fh).

If a fabrication number exists the slave should add this data to the variable data blocks in every RSP-UD telegram. If the fabrication number and enhanced selection is not implemented in a slave this device will not confirm the enhanced selection telegram and will be deselected.

Enhanced selection should be used only if the normal kind of selection is not successful.

98.4 Searching for Installed Slaves

98.4.1 Primary Addresses

To read out all installed slaves the master software must know all the slaves, which are connected to the bus. Therefore the software searches for slaves with primary adressing by sending a REQ_UD2 to all allowed adresses (1..250) with all available baudrates. The master notes used primary addresses with the respective baudrates.

98.4.21 Secondary Addresses

The secondary addressing described in the preceding section draws attention to the problem of determining the secondary addresses of slaves connected to the bus. The master can after this read out the slaves making use of secondary addresses with previous selection. Testing all possible identification numbers with the master software would take years, since the identification number offers millions of combinations. For this reason, a procedure was developed for the rapid and automatic determination of already installed slaves:

98.4.32 Wildcard searching procedure

The following wildcard searching procedure uses the occupation of individual parts of the secondary address with wildcards (Fh) for selection:

In this case with the identification number (BCD) each individual position, and by manufacturer, version and medium (binary coding), only one complete byte, can be occupied with wildcards. The master begins the selection using a SND_UD with the control information 52h (Mode 1), and occupies all positions in the identification number, except the top one, with wildcards. The top position is run through in ten selections from 0 to 9 (0FFFFFFF to 9FFFFFFF).

If after such a selection the master receives no acknowledgement, it then goes to the next selection. If the master receives an E5h, it then sends a REQ_UD2 and learns the secondary address of the slaves from the reply telegram, as long as no collision occurs. If there is a collision after the selection or the REQ_UD2, the master varies the next positions and holds the existing one. If there is a collision, for example at 5FFFFFFF, the selection is run through from 50FFFFFF to 59FFFFFF. If in this case collisions again occur, then a change is made to a variation of the next position. After running through a complete position, the next higher position is processed up to 9.

With this Wildcard searching procedure, it will be seen that at least the top position must be run through in order to reach all slaves. Running through further positions may be necessary, depending on the number of the slaves and the distribution of the identification numbers. This procedure allows a statement of the maximum number of selections in relation to the number of slaves, but as disadvantage frequent collisions, which occur, should be mentioned. The wildcard searching procedure must be performed for all used baudrates and both byte sequences (mode 1 and 2).

The search procedure can be extended with searching for manufacturer, generation and finally device typesmedia to find slaves, which have the same identification number. It is also possible to search for all slaves of a certain manufacturer or all slaves of a certain device typemedia by setting the corresponding value. With extended selection meters which differ only in their manufacturer specific fixed fabrication number can be distinguished.

Appendix A: Coding of Data Records (Normative)

The standard IEC 870-5-4 defines the following data types for usage inside the application layer:

Type A = Unsigned Integer BCD := XUI4 [1 to 4] <0 to 9 BCD>

27

26

25

24

23

22

21

20

 

digit 10

digit 1

1UI4 [1 to 4] <0 to 9 BCD> := digit 100

8

4

2

1

8

4

2

1

2UI4 [5 to 8] <0 to 9 BCD> := digit 101

...

...

...

...

...

...

...

...

...

8

4

2

1

8

4

2

1

XUI4 [5 to 8] <0 to 9 BCD> := digit 10X-1

Digits values of $A-$E in any digit position signals invalid.

A hex code $F in the MSD position signals a negative BCD number in the remaining X-1 digits. For details of this coding see appendix B.

Type B = Binary Integer := I[1..X] <(-2X-1 -1) to +(2X-1-1)>

27

26

25

24

23

22

21

20

1B1 [X] := S=Sign: S<0> := positive

...

           

...

S<1> := negative

S

2X-2

         

2X-8

negative values in twoīs complement

The coding "10000000b" signals "invalid"

Type C = Unsigned Integer := UI[1 to X] <0 to 2X-1>

27

26

25

24

23

22

21

20

UI8 [1 to 8] <0 to 255>

...

           

...

 

2X-1

           

2X-8

 

 

Type D = Boolean (1 bit binary information) := XB1 B1[i] <0 to 1>

27

26

25

24

23

22

21

20

XB1: B1[i] <0 to 1>

...

           

...

B1[i] <0> := false

2X-1

           

2X-8

B1[i] <1> := true

Type E = Compound CP16 (types and units information)

27

26

25

24

23

22

21

20

1UI6[1 to 6] <0 to 63> := physical unit 1

215

214

213

212

211

210

29

28

1UI6[9 to 14] <0 to 63> := physical unit 2

               

1UI4[7,8,15,16] <0 to 15> := measured media

 

Note that this is special coding used only in fixed format data respond. It shall therefore not be used in new developments.

The following data types can only be used with the variable data structure:

Type F = Compound CP32: Date and Time

 

 

 

 

27

26

25

24

23

22

21

20

215

214

213

212

211

210

29

28

223

222

221

220

219

218

217

216

231

230

229

228

227

226

225

224

 

 

 

 

 

 

Type G: Compound CP16: Date

27

26

25

24

23

22

21

20

day:

UI5 [1 to 5] <1 to 31>

"0": every day

215

214

213

212

211

210

29

28

month:

UI4 [9 to 12] <1 to 12>

"15": every month

               

year:

UI7[6 to 8,13 to 16] <0 to 9999> 127: every year

For compatibility with old meters with a circular two digit date it is recommended to consider in any master software the years "00" to "80" as the years 2000 to 2080.

 

 

TType H: Floating point according to IEEE-standard

"Short floating Point Number IEEE STD 754" = R32IEEESTD754

R32IEEESTD754 := R32.23 {Fraction, Exponent, Sign}

Fraction = F := UI23 [1to 23] <0 to 1-2-23>

Exponent = E := UI8 [24 to 31] <0 to 255>

Sign = S := BS1 [32] S<0> = positive

S <1> = negative

F <0> and E <0> := (-1) S * 0 = ± zero

F <¹ 0> and E <0> := (-1) S * 2E-126(0.F) = denormalized numbers

E <1 to 254> := (-1) S * 2E-127(1.F) = normalized numbers

F <0> and E <255> := (-1) S * ¥ = ± infinite

F <¹ 0> and E <255> := NaN = not a number, regardless of S

 

bits

8

7

6

5

4

3

2

1

octet 1

F = Fraction

 

2-16

2-17

2-18

2-19

2-20

2-21

2-22

2-23

octet 2

F = Fraction

 

2-8

2-9

2-10

2-11

2-12

2-13

2-14

2-15

octet 3

E (LSB)

F = Fraction

 

2-0

2-1

2-2

2-3

2-4

2-5

2-6

2-7

octet 4

Sign

E = Exponent

 

S

27

26

25

24

23

22

21

The following ranges are specified by IEE Std 754-1985 for floating point arithmetics:

Range: (-2128 + 2104) to (+2128 - 2104), that is -3.4* 1038 to +3.4*1038

smallest negative number: -2-149, that is: -1.4* 10-45

smallest positive number: +2-149, that is: + 1.4* 10-45

Appendix B: Interpretation of Hex-Codes $A-$F in BCD-data fields

General description

1.) Standard Reference

This standard allows multi-digit BCD-coded datafields. It does however not contain information about what happens if a non-BCD hex code ($A-$F) is detected by the master software.

2.) Purpose of this proposal

a) Define the treatment of non BCD-digits in slave to master RSP_UD-telegrams

To fully define a master software including error treatment such a definition would be desirable.

b) Utilize these codes for simplified error treatment by slave

The current user group proposal contains various techniques for signalling errors or abnormal situations. Most of them are hard to implement on weak mikro-processors. Utilizing these "illegal" codes $A to $F for signalling these states to the master would simplify the software design of the slaves.

c) Anormal states of variables

This happens for example, if a fixed date value is not yet available, because the first fixed date is in the future. The display at the meter or the remote PC should read "----".

This could happen for a temperature variable, if the sensor is malfunctioning. The display at the meter or a remote PC should signal some error code. Multiple error codes should be supported.

Exceeding the upper count limit on integral values or the upper value limit on momentary values should be signallable. For a wrap around carry of integral variables the display should be consistent with old mechanical wrap around counters. In addition a wrap around flag should be extractable.

Underflowing the lower count limit of 00 on integral values or a negative value on momentary values should be signallable. For a wrap around carry of integral variables the display should be consistent with old mechanical wrap around counters. In addition a wrap around flag should be extractable.

To simplify the design of slaves with integrated displays, the above mentioned non-BCD states of the variables should be both transmittable in the form of suitable (Hex) codes but also be displayable directly from the value codes of a 7-segment (usually LCD) display by extending the normal ten entry BCD to 7-segment decoding a table to either a dual 16-entry or a single 32-entry decoding table where 16 entries are used for decoding the MSD (Most Significant Digit) and the other 16 entries are used for the decoding for all other for all other digits. For very weak mikroprocessors with a maximum of a single decoding table with only 16-entries a compatible solution with decreased functionality is also presented.

Recommendation

1.) Definition of hex code meanings

a) $A-$E

Such a code in the MSD (Most significant digit) position signals a one digit value overflow either of a number or due to an addition or increment carry. The display at the meter or a remote PC should display a "0" at the appropriate display position. This makes the display compatible with conventional counter rollover. In addition the leading digit can be treated by the slave software simply as a hexadecimal digit instead of the BCD-coded other digits to realize this function. Processing software in the master could convert this data digit to a value of 10 in an extended length data field. In addition an appropriate application error code could be generated if desired. If this hex code appears in any other digit position than the MSD, it signals a value error of the complete data field. If an alternative display decoding table for the digits other than the MSD is possible, this hex code should be displayed in these other digit positions as the symbol "A". This would allow more flexible displayable error codes.

Example: A 4-digit BCD code of "A321" should be interpreted by the master software as "10321" with an optional overrange VIFE-error code and displayed as 0321 on a 4-digit only display.

b) $B

Such a code in the MSD digit position signals a two digit value overflow either of a number or due to an addtion or increment carry. The display at the meter or a remote PC should display a "1" at the appropriate display position. This makes the display compatible with conventional counter rollover. In addition the leading digit can be treated by the slave software simply as a hexadecimal digit instead of the BCD-coded other digits to realize this function. Processing software could convert this data digit to a value of 11 in an extended length data field. In addition an appropriate application error code could be generated if desired. If this hex code appears in any other digit position than the MSD, it signals a value or availability error of the complete data field. It should be displayed as the symbol "-".

Example: A 4-digit BCD code of "B321" should be interpreted by the master software as "11321" with an optional overrange VIFE-error code and displayed as 1321 on a 4-digit only display with digit selective decoding.

c) $C

Such a code in the MSD digit position signals a three digit value overflow either of a number or due to an addition or increment carry. The display at the meter or a remote PC should display a "2" at the appropriate display position. This makes the display compatible with conventional counter rollover. In addition the leading digit can be treated by the slave software simply as a hexadecimal digit instead of the BCD-coded other digits to realize this function. Processing software could convert this data digit to a value of 12 in an extended length data field. In addition an appropriate application error code could be generated if desired. If this hex code appears in any other digit position than the MSD, it signals a value error of the complete data field. It should be displayed as the symbol "C". Note that the suggested interpretation of $A to $C in the MSD effectivly supports a 30% overrange guard band against an undetected rollover and flexible error codes including the letters "A", "C", "E" and "F".

Example: A 4-digit BCD code of "C321" should be interpreted by the master software as "12321" with an optional overrange VIFE-error code and displayed as 2321 on a 4-digit only display.

d) $D

Such a code in any digit position signals a general error of the complete data field. The display at the meter or a remote PC should display an appropriate symbol blank at the appropriate display position. Since both an overflow from $C and an underflow from $E end in this out of range type error the function of an out-of-range over/underflow can be implemented by simple hex arithmetic. It is however recommended that the slave arithmetic checks this $D-code in the MSD before incrementing or decrementing the value for integral variables to make such an error irreversible if the slave does not expect such an over- or underflow.

 

 

e) $E

Such a code in the MSD digit position signals a two digit value underflow either of a number or due to a subtraction or decrement borrow. The display at the meter or a remote PC should display an "8" at the appropriate display position. This makes the display compatible with conventional counter rollunder. In addition the leading digit can be treated by the slave software simply as a hexadecimal digit instead of the BCD-coded other digits to realize this function. Processing software could convert the data in the field to a negative value using 16īs complement on the leading digit and tens complement at the other digits. In addition an appropriate application error code could be generated if desired. If this hex code appears in any other digit position than the MSD, it signals a value error of the complete data field. It should be displayed as the symbol "E".

Example: A 4-digit BCD code of "E321" should be interpreted by the master software as "- 1679" (F999-E321+1) with an optional underrange VIFE-error code and displayed as 8321 on a 4-digit only display.

bf) $F

Such a code in the MSD digit position signals a "minus-sign" in front of the remaining (N-1) digit number. In any other digit position it signals an error.n one digit value underflow either of a number or due to a subtraction or decrement borrow. The display at the meter or a remote PC should display an "9" at the appropriate display position. This makes the display compatible with conventional counter rollunder. In addition the leading digit can be treated by the slave software simply as a hexadecimal digit instead of the BCD-coded other digits to realize this function. Processing software could convert the data in the field to a negative value using 16īs complement on the leading digit and tens complement at the other digits. In addition an appropriate application error code could be generated if desired. If an alternative display decoding table for the digits other than the MSD is possible, this hex code should be displayed in these other digit positions as the symbol "F". Note that the suggested interpretation of $E and $F in the MSD effectivly supports a 20% underrange guard band against an undetected rollunder for displays and flexible error displays if dual decoding tables are available. In addition it allows a simplified coding for small negative values as often required for values like temperature or flow rate.

Example: A 4-digit BCD code of "F321" should be interpreted by the master software as "- 0321679" (F999-F321+1) with an optional underrange VIFE-error code and displayed as -9321 on a 4-digit only display.

 

g) Combinations

If with the exception of the MSD all other digits are true BCD-digits ($0-$9) the value is either considered as "Overflow" for the MSD hex codes $A to $C or as "Underflow" for the MSD hex codes $E and $F or a general error for the MSD hex code $D.

The code $DBB.. in the data field is always considered as "not available". This is displayed as " ----" (with a blank in the MSD). Any other non BCD-hex codes in one or several digits other than the MSD is interpreted as an error for the complete data field. The error type is formed from the characters "A", "C", "E", "F" (all corresponding to their hex code), "-", blank and the digits 0-9. The display may show an identical error code if displaying the variable, but the MSD digit on the display can contain only blank or the digits 0..9.

h) Decoding table for 2*16 entries (or 32 entries)

 

0

1

2

3

4

5

6

7

8

9

$A

$B

$C

$D

$E

$F

MSD

"0"

"1"

"2"

"3"

"4"

"5"

"6"

"7"

"8"

"9"

"0"

"1"

"2"

" "

"8"

"9"

other digits

"0"

"1"

"2"

"3"

"4"

"5"

"6"

"7"

"8"

"9"

"A"

"-"

"C"

" "

"E"

"F"

 

i) Subset functions

A slave may utilize either non, a single, several or all suggested special functions and their associated hex codes. A slave might utilize also a different number of hex code functions for different data fields. A slave could also use different display implementations for the various special functions and error displays but the suggested solution would simplify the operation of the system, since the master display will be identical to the slave display for the value associated with the appropriate data field.

2.) Recommended LCD-Decoding tableSubset for single 16-entry display decoding

a) Decoding table

0

1

2

3

4

5

6

7

8

9

$A

$B

$C

$D

$E

$F

"0"

"1"

"2"

"3"

"4"

"5"

"6"

"7"

"8"

"9"

"A0"

"b-"

"C"

" "

"E"

"-9"

b) Overrange

The overrange feature should be limited to a 10% overrange ($A in MSD). A further increment should lead directly to the MSD-error hex code $D, which should stop further increment and decrement and generate a suitable error code in the other digits

c) Underrange

The underrange feature should be limited to a 10% underrange ($F in MSD). A further decrement should lead directly to the MSD-error hex code $D, which should stop further increment and decrement and generate a suitable error code in the other digits.

d) Error codes

Error codes may contain only the letters "C" and "E", blank, "-" and the digits 0-9.

e) Compatiblity

At the master side this subset realisation is completely compatible and transparent to the full implementation.

Appendix C: Alarm Protocol (Recommendation)

The formerly described method for an alarm protocol (see diploma work of Andreas Steffens "Eigenschaften und Anwendungen des M-Bus") was based on time slices for each of the maximum 64 alarm devices. This alarm protocol has not been standardized.

We now suggest to return to standard alarm protocol which conforms to the standard IEC 870-2:

The master software polls the maximum 250 alarm devices by requesting time critical data (REQ_UD1 to adresses 1 .. 250). A slave can transmit either a single character acknowledgement E5h signalling no alarm or a RSP_UD with the CI-Field 71h to report an alarm state.

68h

04h

04h

68h

08h

Adr

71h

Alarm State

CS

16h

Fig. 11 Telegram for an Alarm-Respond

The alarm state is coded with data type D (boolean, in this case 8 bit). Set bits signal alarm bits or alarm codes. The meaning of these bits is manufacturer specific.

The timeout for time critical communication must be set to 11..33 bit periods to ensure a fast poll of all alarm devices. With a baudrate of 9600 Bd and all 250 slaves reporting an alarm just in time before a timeout occurs each slave will be polled in periods of maximum 5.5 seconds. This seems to be fast enough for alarms in building control systems and other applications. For faster alarm systems the number of alarm sensors could be limited to 63 (reducing the worst case overall signal delay to less than 1.5 sec or increase the transmission speed to 38400 Bd and achieve the same speed for up to 250 devices.

The functionality of the FCB- and FCV-Bit should be fully implemented in this alarm protocol to ensure that one-time alarms are safely transmitted to the master. If the slave has reported an one-time alarm and the next REQ_UD1 has a toggled FCB (with FCV=1) the slave will answer with an E5h signalling no alarm. Otherwise it will repeat the last alarm frame to avoid that the alarm message gets lost.

Appendix D: Fixed data Structure (Informative, Obsolete)

This alternate data structure has been defined in the first edition of this standard. Due to ist limited flexibility it is not recommend for new developments of meters or other slaves. It is described here for implementing universal master software for the transition period where devices using this protocol are still on the market or in use.

Identification No.

Access No.

Status

Medium/Unit

Counter 1

Counter 2

4 Byte

1 Byte

1 Byte

2 Byte

4 Byte

4 Byte

Fig. 12 Fixed Data Structure in Reply Direction (transmit sequence from left to right)

The Identification Number is a serial number allocated during manufacture, coded with 8 BCD packed digits (4 Byte), and which thus runs from 00000000 to 99999999.

The Access Number has unsigned binary coding, and is increased by one after each RSP_UD from the slave. With the field Status various information about the status of counters, and faults which have occurred, can be communicated - see Figure 16:

 

Bit

Meaning with Bit set

Significance with Bit not set

0

Counter 1 and 2 coded signed binary

Counter 1 and 2 coded BCD

1

Counter 1 and 2 are stored at fixed date

Counter 1 and 2 are actual values

2

Power low

Not power low

3

Permanent error

No permanent error

4

Temporary error

No temporary error

5

Specific to manufacturer

Specific to manufacturer

6

Specific to manufacturer

Specific to manufacturer

7

Specific to manufacturer

Specific to manufacturer

Fig. 13 Coding of the Status Field

The field Medium/Unit is always transmitted with least significant byte first and gives the medium measured for both counter states, and the units for each of the two counter states. The units of counter 1 are coded with the first 6 bits of the first byte, and the units of counter 2 with the first 6 bits of the second byte. The coding of the medium is made up of the two highest bits of these bytes, and can therefore have 16 different values (4 bits). Tables to represent the physical units and the coding of the medium are in the appendix.

 

Byte

Byte No. 8 (byte 2 of medium/unit)

Byte No. 7 (byte 1 of medium/unit)

Bit

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

 

Medium

physical unit of counter 2

Medium

physical unit of counter 1

 

MSB

 

MSB

       

LSB

 

LSB

MSB

       

LSB

Fig. 14 Coding of physical unit and medium in fixed data structure (data type E)

To allow transmission of one historic value with one of the two counters the special unit (111110b or hex code share of 3Eh) has been defined. This unit declares that this historic counter has the same unit as the other actual counter.

D.1 Measured Medium Fixed Structure

Value

Field Medium/Unit

Medium

hexadecimal

Bit 16

Bit 15

Bit 8

Bit 7

 

0

0

0

0

0

Other

1

0

0

0

1

Oil

2

0

0

1

0

Electricity

3

0

0

1

1

Gas

4

0

1

0

0

Heat

5

0

1

0

1

Steam

6

0

1

1

0

Hot Water

7

0

1

1

1

Water

8

1

0

0

0

H.C.A.

9

1

0

0

1

Reserved

A

1

0

1

0

Gas Mode 2

B

1

0

1

1

Heat Mode 2

C

1

1

0

0

Hot Water Mode 2

D

1

1

0

1

Water Mode 2

E

1

1

1

0

H.C.A. Mode 2

F

1

1

1

1

Reserved

 

Notes:

1. Record Medium/Unit is always least significant byte first.

2. H.C.A. = Heat Cost Allocator

3. Media from "Gas Mode2" to "H.C.A. Mode2" are defined additionally to EN1434-3 for some existing meters with CI-Field 73h (intentionally mode1), which transmit the multibyte records with high byte first in contrast to the CI-Field. The master must know that these media codes mean mode 2 or high byte first. Further use of these codes for "pseudo media" is not allowed for new developments.

D.2 Table of Physical Units

 

Unit

 

MSB..LSB

Hex code share

Byte 7/8

Unit

 

MSB..LSB

Hex code share

Byte 7/8

h,m,s

 

000000

00

MJ/h

 

100000

20

D,M,Y

 

000001

01

MJ/h

* 10

100001

21

Wh

 

000010

02

MJ/h

* 100

100010

22

Wh

* 10

000011

03

GJ/h

 

100011

23

Wh

* 100

000100

04

GJ/h

* 10

100100

24

kWh

 

000101

05

GJ/h

* 100

100101

25

kWh

* 10

000110

06

ml

 

100110

26

kWh

* 100

000111

07

ml

* 10

100111

27

MWh

 

001000

08

ml

* 100

101000

28

MWh

* 10

001001

09

l

 

101001

29

MWh

* 100

001010

0A

l

* 10

101010

2A

kJ

 

001011

0B

l

* 100

101011

2B

kJ

* 10

001100

0C

m3

 

101100

2C

kJ

* 100

001101

0D

m3

* 10

101101

2D

MJ

 

001110

0E

m3

* 100

101110

2E

MJ

* 10

001111

0F

ml/h

 

101111

2F

MJ

* 100

010000

10

ml/h

* 10

110000

30

GJ

 

010001

11

ml/h

* 100

110001

31

GJ

* 10

010010

12

l/h

 

110010

32

GJ

* 100

010011

13

l/h

* 10

110011

33

W

 

010100

14

l/h

* 100

110100

34

W

* 10

010101

15

m3/h

 

110101

35

W

* 100

010110

16

m3/h

* 10

110110

36

kW

 

010111

17

m3/h

* 100

110111

37

kW

* 10

011000

18

°C

* 10-3

111000

38

kW

* 100

011001

19

units

for HCA

111001

39

MW

 

011010

1A

reserved

 

111010

3A

MW

* 10

011011

1B

reserved

 

111011

3B

MW

* 100

011100

1C

reserved

 

111100

3C

kJ/h

 

011101

1D

reserved

 

111101

3D

kJ/h

* 10

011110

1E

same but

historic

111110

3E

kJ/h

* 100

011111

1F

without

units

111111

3F

Example for a RSP_UD with fixed data structure (mode 1):

The slave with address 5 and identification number 12345678 responds with the following data (all values hex.):

68 13 13 68 header of RSP_UD telegram (L-Field = 13h = 19d)

08 05 73 C field = 08h (RSP_UD), address 5, CI field = 73h (fixed, LSByte first)

78 56 34 12 identification number = 12345678

0A transmission counter = 0Ah = 10d

00 status 00h: counters coded BCD, actual values, no errors

E9 7E Type&Unit: medium water, unit1 = 1l, unit2 = 1l (same, but historic)

01 00 00 00 counter 1 = 1l (actual value)

35 01 00 00 counter 2 = 135 l (historic value)

3C 16 checksum and stop sign

Appendix E: Examples

Example for a RSP_UD with variable data structure answer (mode 1):

(all values are hex.)

68 1F 1F 68 header of RSP_UD telegram (length 1Fh=31d bytes)

08 02 72 C field = 08 (RSP), address 2, CI field 72H (var.,LSByte first)

78 56 34 12 identification number = 12345678

24 40 01 07 manufacturer ID = 4024h (PAD in EN 61107), generation 1, water

55 00 00 00 TC = 55h = 85d, Status = 00h, Signature = 0000h

03 13 15 31 00 Data block 1: unit 0, storage No 0, no tariff, instantaneous volume,

12565 l (24 bit integer)

DA 02 3B 13 01 Data block 2: unit 0, storage No 5, no tariff, maximum volume flow,

113 l/h (4 digit BCD)

8B 60 04 37 18 02 Data block 3: unit 1, storage No 0, tariff 2, instantaneous energy,

218,37 kWh (6 digit BCD)

18 16 checksum and stopsign

The VIFE can be used for actions which shall be done with the data (master to slave, chapter 6.5), for reports of application errors (slave to master, chapter 6.6) and for an enhancement of the VIF (orthogonal VIF, chapter 8.4.5). The last feature allows setting VIFīs into relation to the base physical units (e.g. VIF=10 liter, VIFE= per hour) or coding indirect units, pulse increments and change speeds.

In case of VIFE = FFh the next VIFE's and the data of this block are manufacturer specific, but the VIF is coded as normal.

After a VIF or VIFE with an extension bit of "0", the value information block is closed, and therefore also the data record header, and the actual data follow in the previously given length and coding.

Example baud rate switch:

The master switches the slave (in point to point connection) from now 2400 baud to 9600 baud.

Master to slave: 68 03 03 68 | 53 FE BD | 0E 16 with 2400 baud

Slave to master: E5 with 2400 baud

From that time on the slave communicates with the transmission speed 9600 baud, if the
slave can handle 9600 baud, otherwise it remains at 2400 baud.

In busmode this must be followed within < 2min by an acknowledged communication (i.e. SND_NKE) at 9600 baud:

Master to slave: 10 40 FE 3E 16

Slave to master: E5

Example Reset with subcode:

The master releases an enhanced application reset to all slaves. All telegrams of the user data type are requested.

Master to Slave: 68 04 04 68 | 53 FE 50 | 10 | B1 16

Slave to Master: E5

E.2 Writing Data to a Slave

The master can send data to a slave using a SND_UD with CI-Field 51h for mode 1 (or 55h for old mode 2-meters). Note that the data structure in such a write telegram has been changed in contrast to previous definitions by means of leaving out the fixed data header of 12 byte. The following figure shows the data structure for a write telegram. The order of the first three blocks in the following figure can be turned round, but the write only data record must be at the end of the telegram. All records are optional.

Primary Address Record

Enhanced Identifica-

tion Record

Normal

Data Records

Write Only Data Records

Fig. 15 Data Structure for Writing Data

· Primary Address Record:

The primary address record is optional and consists of three bytes:

DIF = 01h

VIF = 7Ah

Data = Address (1 byte binary)

With this data record a primary address can be assigned to a slave in point to point connections. The master must know all the used addresses on the bus and forbid setting the address of a slave to an already used address. Otherwise both slaves with the same address couldnīt be read out anymore.

· Enhanced Identification Record:

With this optional data record the identification (secondary address) can be changed. There are two cases to be distinguished:

1) Data is only the identification number

DIF = 0Ch

VIF = 79h

Data = Identification No. (8 digit BCD)

2) Data is the complete identification

DIF = 07h

VIF = 79h

Data = complete ID (64 bit integer)

The data is packed exactly as in the readout header of a $72/$76 variable protocol with low byte first for mode 1 and high byte first for mode 2:

 

Identification No.

Manufacturer ID

Generation

Medium

 

4 byte

2 byte

1 byte

1 byte

 

· Normal Data Records:

The data records, which can be read out with a REQ_UD2, are sent back to the slave with the received DIF and VIF and the new data contents. Additional features can be implemented using the generalized object layer (see chapter 6.5).

· Write-Only Data:

Data, which cannot be read out of the slave with a normal data block, can be transmitted using the VIF = 7Fh for manufacturer specific coding. The DIF must have a value corresponding to the type and length of data.

After receiving the SND_UD correctly without any error in data link layer the slave must answer with an acknowledgement (E5h). The slave decides whether to change variables or not after a data write from the master. In case of errors in executing parts of or whole write instructions the slave can decide whether to change no variables or single correct variables. The slave can report the this errors to the master in the next RSP_UD telegram using some of the methods which are described in chapter 6.6.

There are some methods for implementing write protect, for example allowing only one write after a hardware reset of the processor or enabling write if a protect disable jumper is set.

Examples:

1. Set the slave to primary address 8 without changing anything else:

68 06 06 68 | 53 FE 51 | 01 7A 08 | 25 16

2. Set the complete identification of the slave (ID=01020304, Man=4024h (PAD), Gen=1, Med=4 (Heat):

68 0D 0D 68 | 53 FE 51 | 07 79 04 03 02 01 24 40 01 04 | 95 16 §

3. Set identification number of the slave to "12345678" and the 8 digit BCD-Counter (unit 1 kWh) to 107 kWh.

68 0F 0F 68 | 53 FE 51| 0C 79 78 56 34 12 | 0C 06 07 01 00 00 | 55 16

E.3 Configuring Data Output

For default the slave transmits all his data with a RSP_UD. It could be useful for some applications to read only selected data records out of one or more devices. There are two ways to select data records:

 

Selection without specified data field

The selection of the wanted data records can be performed with a SND_UD (CI-Field = 51h/55h) and data records containing the data field 1000b, which means "selection for readout request". The following VIF defines the selected data as listed in EN1434-3 and no data are transmitted. The answer data field is determined by the slave. The master can select several variables by sending more data blocks with this data field in the same telegram.

Special multiple values can be selected with the following methods:

· Any VIF:

The VIF-Code $7E (any VIF) is especially for readout request of "all VIF" from the slave and can be interpreted as a selection wildcard for the value information field.

· Global readout request:

The DIF-Code $7F is defined as "selection of all data for readout request", i.e. all storage numbers, units, tariffs and functions. If this DIF is the last byte of user data or the VIF=$7E follows, then all data is requested. So the selection of all data of one slave can de done with a SND_UD and the character $7F as the user data. If there follows a DIF unequal to $7E, then all subfields of this VIF are selected for readout.

· All Tariffs:

The highest tariff number in the selection record is defined as selection of "all tariffs". For example the tariff 1111b (15) means selection of all tariffs in a record with two DIFEīs.

· All Storage Numbers:

A selection of all storage numbers can be done with the maximum storage number if there is a minimum of one DIFE. For example the highest storage number is $1F (31) with one DIFE and $1FF (511) with two DIFEīs.

· All Units:

"All units" can be selected by using a data record header with minimum two DIFEīs and the highest unit number.

· High Resolution Readout:

The master can select the slave to answer with the maximum resolution to a given value / unit by a VIF with "nnn" = 000 (minimum exponent for range coding). The meter may then answer with a resolution of e.g. 1mWh (VIF=0000000b) or some higher decimal value if required. The unit values have been chosen so that their minimum provides sufficient resolution even for calibration. A readout request for a VIF with "nnn"=max (maximum exponent for range coding) signals a request for the standard resolution of the meter.

After the next REQ_UD2 the slave answers with the selected data in his own format, if the requested data are available. Otherwise the slave transmits his normal data and the master has to find out that the data are not the requested one. If there are more than one variables with the selected VIF, the device should send all these data records.

Selection with specified data field

The master is able to perform a readout request with a specified data field by using the object action "add to readout list" (VIFE = E000 1100b) from VIFE-table for object actions (see chapter 7, table 176.5). The master transmits a SND_UD (CI-Field = 51h/55h) with a data record which consists of the desired DIF (data field), VIF and the VIFE = 0Ch / 8Ch. No data follows this VIFE and the slave should ignore the data field on reception. The slave should transmit this data record with the requested data field from now on, if he is capable of this. If the slave doesnīt support this data field (data coding), it can report a record error using one of the VIFE = E000 011x (data class not implemented or data size not implemented).

Deselection of data records

The master can release a reset of the application layer and especially a fallback to the slaves standard RSP_UD-Telegram by transmitting a SND_UD with the CI-Field $50.

Single data records can be deselected by transmitting a data record with DIF, VIF and the VIFE for the object action "Delete from Readout-List" (VIFE = E000 1101b).

If the selected data is supported by the slave but too long for one RSP_UD telegram (especially for readout of all historic values), the slave transmits an additional data record consisting only of the DIF=$1F, which means that more data records follow in the next respond telegram. In this case the master must readout the slave again until the respond telegram is only an $E5 (no data) or there is no DIF=$1F in the RSP_UD.

To avoid lost of data respond telegrams the slave should in this case support the Frame Count Bit (FCB). If the master wants to premature end such a multitelegram sequential readout of the selected data, it may send an application reset with CI=$50 instead of further REQ_UD2īs.

Examples:

1. A slave with address 7 is to be configured to respond with the data records containing volume (VIF=13h: volume, unit 1l) and flow temperature (VIF=5Ah: flow temp.,

unit 0.1 °C).

68 07 07 68 | 53 07 51 | 08 13 08 5A | 28 16

 

2. A slave with address 1 is to be configured to respond with all storage numbers, all tariffs,

and all VIFīs from unit 0.

68 06 06 68 | 53 01 51 | C8 3F 7E | 2A 16

3. A slave with address 3 is to be configured to respond with all data for a complete readout of all available. After that the master can poll the slave to get the data.

68 04 04 68 | 53 03 51 | 7F | 26 16

With these actions the master can alter the data of the slaves or configure the output data of the slaves (actions 12 and 13). The actions 0 to 6 alter the data of the slave by replacing the old data (action 0, equals to data write without VIFE) or do arithmetical or logical operations with the old and the transmitted data.

Note that this method of configuring the readout list (action 12 and 13) allows not only the adding but also the removal of elements in contrast to the method of using the DIF=1000b-type of readout request (described beforein chapter 6.4.3).

All these actions can be used for normal slaves and for intelligent master which are manipulated by a higher order master.

The functions "Add entry" and "Delete entry" are useful to tell an intelligent master to add e.g. a new data record like maximum or minimum values of any slave.

With the action "freeze data to storage #" the master can tell the slave to freeze the actual value corresponding to the transmitted VIF, unit, tariff and function to a certain storage number given in the DIF/DIFEīs. In this case the data field inside the VIF has got the value 0000b (no data). This action allows freeze of selected values or multiple freeze with VIF=$7E (all VIF). The date / time should also be freezed to the same storage number.

Examples:

1) Set the 8 digit BCD-Counter (instantaneous, actual value, no tariff, unit 0) with VIF=06 (1kWh) of the slave with address 1 to 107 kWh.

68 0A 0A 68 | 53 01 51 | 0C 86 00 07 01 00 00 | 3F 16

2) Same as in example 1) but add 10 kWh to the old data.

68 0A 0A 68 | 53 01 51 | 0C 86 01 10 00 00 00 | 48 16

3) Add an entry with an 8 digit BCD-Counter (instantaneous, actual value, no tariff,

unit 0, 1kWh) with the start value of 511 kWh to the data records of the slave with address 5.

68 0A 0A 68 | 53 05 51 | 0C 86 08 11 05 00 00 | 59 16

4) Freeze actual flow temperature (0.1 °C: VIF = 5Ah) of the slave with address 1

into the storage number 1.

68 06 06 68 | 53 01 51 | 40 DA 0B | CA 16

E.4 Slave Collision Detect

Collisions between transmitting slaves can occur during slave search activities by the master. Very light collisions of (22..33) mA, which are equivalent to 2 or 3 transmitting slaves, are electrically undetectable by master and slave. New master hardware with double current detect can detect light collisons of (20..200) mA and then transmit a break (50 ms space) on the bus. The slave can detect medium collisions of (70..500) mA, if this is a collision between a mark and a space and if the slave supports this feature. Heavy collisions of (90..5000mA) will have the effect of a break down of the bus voltage (power fail in the slave) and possibly a shortcircuit in the master.

To avoid these consequences of (heavy) collisions new master have the feature of double current detect with break signaling and switching off the bus in overcurrent states. There are some means for the slaves to detect collisions and then stop transmitting:

 

1. Software based UARTīs can test at the end of each Mark-Send-Bit whether the input is really a mark. This guarantees a very fast detection of collisions, is simple to implement and is strongly recommended for pure software UART.

2. A variation of the preceeding method is to test whether the bus voltage is mark after each stop-bitdirectly before the transmission of each start bit. This is simple for a software UART, but very tricky for a hardware UART and requires a master sending a break on collision detect.

3. A simple method for unbuffered hardware UART, but tricky for buffered hardware UART, is to compare the transmitted with the received byte.

4. Another method, which requires a master with break collision detect, is a hardware UART with break detect.

5. The baudrate of the communication process after a detected break will be 300 Baud § .

 

E.5 FCB-Bit and Selection

FCB-Implementation slave

A slave with implemented secondary addressing and with implemented FCB-administration must have an additional set of 0, 1 or 2 separate "Last Received FCB"-memory Bit(s) for all communication via the pseudo primary address 253 ($FD). If it can communicate also alternatively over some other primary address (exept the special addresses 254 and 255) an additional set of 0, 1 or 2 "Last received FCB"-memory bit(s) for each of these primary addresses is required. A valid selection telegram will not only set the internal selection bit but will also clear all 0, 1 or 2 internal "Last received FCB"-memory bit(s) associated with secondary addressing via the pseudo primary address 253 ($FD). The master will start the communication (REQ_UD2 or SND_UD) after any selection telegram (CI=$52 or $56) with the FCV-Bit set and the FCB-Bit set. If a slave has more than one alternative secondary identification, only a single set of 0, 1 or 2 "Last received FCB"-memory bit(s) for all secondary addresses is required.

FCB-Implementation master

The master must implement a separate pair of "Next FCB image"-Bits for pseudo primary address 253 ($FD) as for each other primary address. Although these "Next FCB image"-bits might be used for many slaves, no confusion exists, since for accessing another slave a selection telegram is required which will define the future FCB sequence both for slave and master.

E.6 Special Slave Features

Some optional or recommended features of the slaves will be described in this section.

E.6.1 Use of the fabrication Number

The fabrication number is a serial number allocated during manufacture. It is part of the variable data block (DIF = $0C and VIF = $78) and coded with 8 BCD packed digits (4 Byte).

Example:

68 15 15 68 header of RSP_UD telegram (length 1Fh=31d bytes)

08 02 72 C field = 08 (RSP), address 2, CI field 72H (var.,LSByte first)

78 56 34 12 identification number = 12345678

24 40 01 07 manufacturer ID = 4024h (PAD in EN 61107), generation 1, water

13 00 00 00 TC = 13h = 19d, Status = 00h, Signature = 0000h

0C 78 04 03 02 01 fabrication number = 01020304

9D 16 checksum and stopsign

The use of this number is recommended if the identification number is changeable. In this case two or more slaves can get the same secondary adress and can not be uniquely selected. The fabrication number together with manufacturer, version and medium field build an unique number instaed. Suitable masters use this number for an enhanced selection method if two or more slaves have the same identification numbersecondary adress (see chapter 9.37.4).

Appendix F: Secondary Search

The company Aquametro AG has simulated such a search to find the minimum, the average and the maximum number of selections as a function of the number of slaves. For the minimum number of attempts the optimum distribution of the identification numbers was chosen, for the maximum number the most unfavourable, and for the average number of attempts a random distribution. The following diagram shows the result of these calculations:

 

Fig. 16 Number of Selections with Wildcard Searching Procedure

Instructions for implementation of Wildcard Search

The following program flow diagram shows the realization of the Wildcard searching procedure, whereby the search is made only with the identification number. The codes for manufacturer, version and medium are in general specified with wildcards, but can be changed by the user in order (for example) to locate all meters from a particular manufacturer. In order to avoid the categorisation by a factor of eight of the "For-To" loops for the eight positions, the array "Value" is defined with 8 byte numbers, which are intended to define the contents of the positions. The digit number of the identification number which is presently running is noted in the variable "Pos" of type byte.

Fig. 17 Flow Diagram for Slave Search with Wildcards

The routine begins at the first position, and implements the following actions for the value of this position from 0 to 9:

· Selection with the ID-Nr. Pos 1, Pos 2, ........, Pos 8

· if no reply, Value [Pos] is raised by 1

· if there is a reply, a REQ_UD2 is sent to address 253, and if the telegram is correctly received the secondary address is learnt and the Value [Pos] raised by 1

· if there is a collision a jump is made to the next position (Pos increased by 1), as long as the last position has not yet been reached

· after going through a complete position from 0 to 9 the subroutine proceeds to the next lower position, or ends the search if the position Nr. 1 has already been processed

Example

The next figure shows an example for secondary addresses in order from top to bottom, as they will be found by the master software:

No.

Identification-Nr.

Manufacturer. (hex.)

Version (hex.)

Device typeMedia (hex.)

1

14491001

1057

01

06

2

14491008

4567

01

06

3

32104833

2010

01

02

4

76543210

2010

01

03

Fig. 18 Secondary Addresses found with a Wildcard Search of Four Slaves

Search Process:

1. Start with ID = 0FFFFFFF : no reply

2. ID = 1FFFFFFF : collision between Nr.1 and Nr.2

3. ID = 10FFFFFF, 11FFFFFF, 12FFFFFF, 13FFFFFF : no reply

4. ID = 14FFFFFF : collision between Nr.1 and Nr.2

5. Repeated steps 3 to 4 up to the ID = 1449100F

6. Learn ID = 14491001 and 14491008

7. Go backwards to 19999999

8. ID = 2FFFFFFF : no reply

9. ID = 3FFFFFFF : learn ID = 32104833

10. ID = 4FFFFFFF, 5FFFFFFF, 6FFFFFFF : no reply

11. ID = 7FFFFFFF : learn ID = 76543210

12. ID = 8FFFFFFF, 9FFFFFFF : no reply

13. End of the Search

 

Enhanced selection with fabrication number §

The identification number can be used as is a customer number and then can be changed by the operatormaster. Therefore it can be possible that two slaves have the same secondary adress. For this reason the selection telegram can be extended by a fabrication number to make sure that in any case all slaves are distinguishabledevide such slaves. This number is a serial number allocated during manufacture, coded with 8 BCD packed digits (4 Byte) like the identification number, and thus runs from 00000000 to 99999999.

The following figure shows the structure of an enhanced selection telegram released by the master.

68h

11h

11h

68h

53h

FDh

52h

ID1-4

Man1-2

Gen

Med

0Ch

78h

Fab1-4

CS

16h

Fig. 19 Structure of a telegram for enhanced selection (mode 1)

After the field medium the new data is given in form of a structured datarecord with DIF=0Ch and VIF=78h. Parts of the fabrication number (Fab1..Fab4) can be occupied with wildcards (Fh).

If a fabrication number exists the slave should add this data to the variable data blocks in every RSP-UD telegram. If the fabrication number and enhanced selection is not implemented in a slave this device will not confirm the enhanced selection telegram and will be deselected.

Enhanced selection should be used only if the normal kind of selection is not successful.

Appendix G: References

[1] Färber, G. : Bussysteme, R.Oldenbourg Verlag München Wien, 1987

[2] Gabele, E., Kroll, M., Kreft, W. : Kommunikation in Rechnernetzen, Springer Verlag
Heidelberg, 1991

[3] Steffens, Andreas : Diplomarbeit " Der M-Bus - Eigenschaften und Anwendungen", University of Paderborn, Department of Physics, 1992

[4] Texas Instruments Deutschland GmbH : Data Sheet TSS 721, 1993

[5] Texas Instruments Deutschland GmbH : Seminar Material, M-Bus Workshop, 1992

[6] Ziegler, Horst : Seminar Material, M-Bus Workshop, 1992

[57] IEC 870-5-1 : Telecontrol Equipment and Systems, Part 5 Transmission Protocols, Section One - Transmission Frame Formats, 1990

[68] IEC 870-5-2 : Telecontrol Equipment and Systems, Part 5 Transmission Protocols, Section Two - Link Transmission Procedures, 1992

[9] EN1434-3: Heat Meters, Part 3 Data Exchange and Interface, 1997 §

[10] Aquametro AG Therwil : M-Bus Automatic Slave Recognition with Wildcard Algorithm, 1992

[11] Papenheim, Andreas: Diplomarbeit " Anwendungsbeispiele für den M-Bus", University of Paderborn, Department of Physics, 1993

[712] Texas Instruments Deutschland GmbH: Applications Report "Designing Applications for the Meter-Bus", 1994 (translation of reference [11])

[813] Ziegler, Horst; Froschermeier Günther: "M-Bus: Die Meßbus-Alternative", Elektronik 16/1993

Note that a WWW-server operated by the m-bus-user group at "http://www.m-bus.com" provides a forum for up to date information on the M-bus.